An "a" contact - is one that it
is open when the breaker contacts are open and closed when the breaker
contacts are closed.
A "b" contact - is one that is
closed when the breaker contacts are open and open when the breaker contacts
are closed.
Accessory (device) - an electrical or mechanical device that performs
a secondary or minor function apart from overcurrent protection.
Accessory high-fault protector - a self contained unit housing fuses
or high-fault protectors. It is constructed for use with specific breakers
and to be connected directly to the load terminals of the breaker.
Adjustable circuit breaker - a circuit breaker that can be set to
trip at various values of current, or time, or both within a predetermined
range.
AIR (ampere interrupting rating) - the highest current at rated
voltage that an overcurrent protective device is intended to interrupt under
specified test conditions (NEC).
AFCI (arc-fault current interrupter) - a circuit interrupter that
detects a wide range of arc-fault conditions.
Alarm switch (bell alarm) - see overcurrent trip switch.
Ambient temperature rating - temperature at which the continuous
current rating (handle rating) of a circuit breaker is based; the
temperature of the air immediately surrounding the circuit breaker which can
affect the thermal (overload) tripping characteristics of thermal-magnetic
circuit breakers.
Auxiliary switch - a switch mechanically operated by the main device
for signaling, interlocking, or other purposes.
Bell alarm - see overcurrent trip switch.
Branch circuit - the circuit conductor between the final overcurrent
device protecting the circuit and the outlet(s).
Circuit breaker - a device designed to open and close a circuit by
non automatic means and to open the circuit automatically on a predetermined
overcurrent without injury to itself when properly applied within its
ratings.
Coil clearing switch - a mechanically operated switch in series with
the coil of a shunt trip device which breaks the coil current when the
circuit breaker opens.
Continuous current rating (handle rating) - the designated rms
alternating current in amperes which a device or assembly will carry
continuously in free air without tripping or exceeding temperature limits.
Continuous load - a load where the maximum current on the circuit is
expected to continue for more than 3 hours.
CSA - Canadian Standards Association.
Current path (of a circuit breaker) - the current-carrying conductors
within a circuit breaker between, and including, line and load terminations.
Current-limiting circuit breaker - a breaker that does not employ a
fusible element and that when operating within its current-limiting range,
limits the let-through I*I*t to a value less than the I*I*t of a half cycle
wave of the symmetrical prospective current.
Current-limiting range - the rms symmetrical prospective currents
between the threshold current and the maximum interrupting rating current.
Current rating - see continuous current rating.
Electrical operator - a controlling device that is used to open,
close, and reset a breaker.
Frequency - the number of cycles per second for an alternating
current system.
Frequency rating - the range of frequencies within which a product
can be applied.
Fused circuit breaker - a breaker that contains replaceable fuses or
high-fault protectors provided to increase the fault current interrupting
ability of the breaker.
Ground fault - an unintentional current path, through ground, back to
the source.
Handle rating - continuous current rating.
High-fault protector - a unit containing a fusible element intended
for mounting in a fused breaker or accessory protector.
High interrupting rating - an interrupting rating in rms symmetrical
amperes at one or more of the values listed in Table 15.
Instantaneous pickup - the current level at which the circuit breaker
will trip with no intentional time delay.
Integral ground-fault protection - equipment ground-fault protection
on grounded neutral systems provided by components internal to the circuit
breaker.
Interrupting rating - the highest current at rated voltage available
at the incoming terminals of the circuit breaker. When the circuit breaker
can be used at more than one voltage, the interrupting rating will be shown
on the circuit breaker for each voltage level. The interrupting rating of a
circuit breaker must be equal to or greater than the available short-circuit
current at the point at which the circuit breaker is applied to the system.
Inverse time - a qualifying term indicating there is purposely
introduced a delay in the tripping action of the circuit breaker, which
delay decreases as the magnitude of the current increases.
Instantaneous-trip circuit breaker - a circuit breaker designed to
trip only under short-circuit conditions.
I*I*t (amperes squared seconds) - Is an expression related to the
energy available as a result of current flow, meaningful only for adiabatic
conditions and as used in this Standard means the I*I*t between the
initiation of the fault current and the clearing of the circuit.
Lock-off device - a device supplied as a kit for field installation
on a breaker used in a motor circuit to permit the breaker to be padlocked
in the OFF position when required by the Canadian Electrical Code, Part I.
Moulded case circuit breaker - a circuit breaker which is assembled
as an integral unit in a supportive and enclosed housing of insulated
material.
Molded case switch - a device designed to open and close a circuit by
non-automatic means that is not intended to provide overcurrent protection.
Overcurrent - any current in excess of the rated continuous current
pf equipment or the ampacity of a conductor.
Overvoltage trip device - a trip mechanism that causes a breaker to
open automatically if the voltage across the terminals of the trip coil
rises above a predetermined value.
Prospective current (available current) - the current that would flow
during a short circuit if the breaker and the wires used for its connection
were replaced by a solid conductor of negligible impedance.
RMS - root-mean-square.
RMS current sensing - a method of determining the true rms current of
sinusoidal and non-sinusoidal waveforms.
SWD circuit breaker - a breaker rated at 15 or 20 A, 347 V or less,
intended to switch fluorescent lighting loads on a regular basis.
Shunt-trip device - a trip mechanism energized by a source of
voltage, that may be derived either from the main circuit or from an
independent source.
Thermal Trip - a trip element consisting of a bimetal that bends
because of the heat generated by current passing through it.
The bimetal's bending force and deflection trips the circuit breaker during
overload conditions.
Threshold current - the rms symmetrical prospective current at the
threshold of the current-limiting range, where the peak current let- through
in each phase is less than the peak of that symmetrical prospective current
and the I*I*t in each phase is less than the I*I*t of a half cycle wave of
the symmetrical prospective currant.
Undervoltage-trip device - a trip mechanisms that causes a breaker to
open automatically if the voltage across the terminals of the trip coil
falls below a predetermined level.